Siemens SGT 400 DLE, 12 MW Generator drive package

Sold

Siemens SGT 400 DLE, 12 MW Generator drive package

Poeldijk, Netherlands

Description

NEW, 0 starts, 0 operating hours, never installed.


General information:

Power rating 12 MW

Generator drive, 11 Kv, 50 Hz

Allen Bradley Control system

Natural gas fired

Outdoor package


Detailed information:

Siemens SGT400, (12,9MW) Gas Turbine package:

Natural gas fired

DLE Combustion

Twin shaft engine

Left hand exhaust


Reduction Gear: 

Epicyclic reduciton gear

Baseplate mounted

Hydraulic start drive

Main drive coupling


A.C. Generator and AVR:

11.0 kV, +/- 10%, 3 phase, 50 Hz, 1500 rpm

-0,35 to + 0,4 power factor

Class F insulation and class B total temperature rises

Voltage transformers – class 0,5, current transformers – Class 0,2 and 5P10

Basler AVR


Integral Lub Oil System:

Supplies gas turbine, reduction gear and A.C. generator

Prining and main oil pumps

A.C. auxiliary pump

D.C. emergency pump

Lub oil vent oil mist eliminator


Gas fuel system:

Double block and bleed valves and rigid pipework

Fuel control valves (pilot and main)

External block and vent valves


Electro – HydraulicGas Turbine Start System:

400V electric motor

Hydraulic pump and motor

Control valves


Dual Mode Compressor Wash System:

To allow for ‘cranked’ washing

High pressure compressed air wash module

Control valves and pipework

Quick-disconnect connector at skid edge

Mobile tank

Low ambient air temperatures protection


Outdoor Acoustic Enclosure 80dB(A):

Standard colour RAL 7032

Access doors, apertures, gland plates

Interior lighting and inspection windows

Removable panels for alternator removal

Turbine exhaust shroud


Enclosure Vent System 80 dB(A):

Vent system for gas turbine / reduction gear

2-stage static filters (F5 & F8)

Negative pressure enclosure

ATEX extraction fan (Zone 2)

Attenuators

Weather protection


Turbine Air Intake System 80dB(A):

Rain / snow ingress protection

Heated vane separator anti icing system


3 stage static air filtration:

1st stage panel filters (F5)

2nd stage panel filters (F8)

3rd stage panel filters (E11)

Attenuation, ductwork and compensator

Support steelwork


Air Inlet Filter Access Platform:

Ladders

Handrails

Kick plates


A.C. Genrator Vent System 80dB(A):

2 stage static filters (F5 & F8)

Attenuation and compensator


Oil Cooler air Blast System 80dB(A):

Single Axial flow fan

Cooler matrix

Attenuation


Control Cabin:

Houses unit control panel suite and CO2 extinguishant

Interior lighting

Air conditioned


Exhaust System:

Side exit

Primary compensator

Thermal / acousting shroud

75dB(A) silencer


Fire Protection and Gas Detection Systems:

Four zone fire monitoring equipment

CO2 storage and CO2 discharge nozzles

Infra-red (3) and heat (rate/rise) detectors (2)

Shut off damper t ventilation system discharge

Two-leverl gas detection

EN54 / ISO6183 compliant


On-Skid Control Panels:

Comprising of the following:

Gas Turbine Control and Protection Section

Allen Bradley “Controllogix” plc

Digital engine management system

Off-skid remote PC for client interface and control

Control, monitoring and protection (pressures, temperatures, vibration etc.)

Remote communication

System graphics

On-skid HMI

Modular distributed I/O

Data communication link (Modbus protocol over TCP/IP


Motor Control Centre:

Single 400V, 50Hz, 3ph connection

A.C. power distribution for the generator set

Motor starters and protection

Distribution MCB’s for auxialiary a.c. supplies

Skid-mounted allowing a single point of contract for the customer


Battery Charger annd Uninterruptible Power Supply:

Battery chargern and UPS 24Vdc supply to control system

Power to lube oil pump for 3 hours after loss of a.c. supply

Maintenance free batteries

Generator Control and Protection Section:

Electronic Automated Voltage Regulator

Digital integrated Protection Relay, comprising:

Differential fault (87G/T)

Stator Earth Fault (51N)

Overcurrent (51)

Three phase over voltage (59)

Three phase under voltage (27)

Reverse Power (32)

Underfrequency (81U)

Overfrequency (81O)

Loss of excitation (40)

Negative Phase Sequence (46)


Synchronisation Equipment:

Auto and check synchronisers

Selector switeches, bus voltmeter and synchroscope

Automatic or manual forwar and back synchronising

MW circuit breaker control

Specifications

ManufacturerSiemens
ConditionNew